Technical
Particulars |
36 KV VCB |
12 KV VCB |
|
Rated Voltage |
36 KV |
12KV |
|
Rated Frequency |
50 Hz |
50 Hz |
|
Rated Normal Current |
1600A |
1250A |
|
No.
of Pole |
3 |
3 |
|
Installation |
Outdoor |
Outdoor |
|
Rated Short Circuit Interrupting
Capacity |
25KA |
25KA |
|
Rated Short Circuit Making
Capacity |
62.5 KA |
62.5 KA |
|
Rated Short Time Current for 3
Sec. |
25KA |
25KA |
|
Phase to Phase Spacing |
400 mm |
300 mm |
|
Creep age Distance of Support
Insulator |
900 mm |
300 mm |
|
Rated Insulation Level |
170 KV |
75 KV |
|
Power Frequency Withstand
Voltage |
70 KV |
28 KV |
|
No.
of Auxiliary Contacts |
10 NO + 10 NC |
10 NO + 10 NC |
|
Metering |
Hot Dip Galvanized lattices
steel support structure |
|
Type
of Insulation |
Porcelain |
Porcelain |