Manufactured under technical collaboration
eith CETEM Spa of Italy. The LBS is rated
for 12KV 630A and having short time current
of 25KA. Ring main unit will be of indoor or
outdoor type, can be made extensible on both
sides and will consist of 2 units of 12KV
630A load break switch coupled with one unit
of load break switch fuse unit or a vacuum
circuit breaker. The load break switch is
provided with fuse tripping arrangement so
that in the event of blowing of HRC fuse the
swicth will be tripped automatically. The
load break switch with modified contacts are
also suitable for capacitive current
breaking of 200A at 12KV.
|